亿鸽在线客服系统

wisdomsystem@163.com

0755-86317046

Language
Design Scheme of Modular Battery Monitoring System
Date:2026-03-04 Count:792

One Typical applications:
ADU3000-APP-SMALL.jpg
II Equipment List:

(1)a set12V/40List of Battery Pack Equipment

name

Module model/specification

quantity

unit

Remarks

Communication management module

BMS100

1

Taiwan

Each module manages 48 batteries

Battery monitoring module (12V battery)

BMS-12

40

Taiwan

Each battery is equipped with one

battery connecting wire

JZ30

40

item

Each battery is equipped with one

Collection module communication cable

BL01

40

item

Each battery is equipped with one

Hall Current Sensor

4-20mA signal

1

a

4-20mA output signal

Battery temperature probe

0-2.5V signal

40

a

Each battery is equipped with one

(2)a set2V/192sectionUPSList of battery pack equipment

name

Module model/specification

quantity

unit

Remarks

Communication management module

BMS200

1

Taiwan

Each module manages 250 batteries

Battery monitoring module (2V battery)

BMS-02

192

Taiwan

Each battery is equipped with one

U-shaped battery connection cable

JZ30

192

only

Each battery is equipped with one

Collection module communication cable

BL01

192

a

Each battery is equipped with one

Hall Current Sensor

4-20mA signal

1

a

4-20mA output signal

Battery temperature probe

0-2.5V signal

192

a

Each battery is equipped with one

III Cable specification requirements:

name

Specification requirements/model

Remarks

12VPower cord and cable

300V RVV -2*0.5mm2cable

CCCCertification national standard line

RS485Communication cable

300V RVVP-2*0.5mm2  Twisted-Pair Cable

CCCCertified national standard line, shielding layer grounded for protection

Current sensor cable

300V RVVP-3*0.5mm2  cable

CCCCertified national standard line, shielding layer connected to signal ground

battery connecting wire

JZ30

Factory configured

Module communication line

BL01

Factory configured

Surface temperature sensor cable

3*0.25mm2  cable

Factory configured