(1) Provide a 1-channel detection cable interface and connect it to a 2-core water leakage detection cable.
(2) Real time response is fast, with a response time of less than 3 seconds.
(3) The monitoring range is wide, and the maximum detection distance can reach 200m.
(4) The detection sensitivity is set by a dip switch, which can adapt to leak detection of different water quality.
(5) Provide alarm sound output, which can be turned on or off by setting the dip switch.
(6) It has 1 relay output for outputting alarm signals or leakage control.
(7) Equipped with 2 LED status indicators, it can quickly and intuitively understand the working status of the leakage detection system.
(8) The port has EMC design, strong anti-interference ability, and high long-term stability.
(9) The DIN rail installation method is convenient for construction and installation.
|
working conditions
|
power input
|
12V, Voltage range 10-30VDC
|
|
operating current
|
≤0.1A
|
|
ambient temperature
|
-20℃~70℃
|
|
ambient humidity
|
10%~90%RH
|
|
water leak detection
|
Number of detection channels
|
1 Road
|
|
Cable length
|
<100m
|
|
detection sensitivity
|
8 sensitivity levels can be set
|
|
response time
|
<3s
|
|
relay output
|
1 channel, contact DC30V 1A
|
|
Testing water quality
|
Ordinary tap water
|
|
EMC Metrics
|
Electrostatic protection
|
Contact discharge: ± 6KV; Air discharge: ± 8KV
|
|
EFT protection
|
±2KV
|
|
external structure
|
Length × Width × Height
|
88*37*59 mm
|