Tel:
0755-86317046,86604023Fax:
0755-86317069
(5) accessible4Core leakage cable with wire breakage detection function;
(6) Fast real-time response, response time<2s;
(7) Wide monitoring range, maximum detection distance can reach300m;
(8) The detection sensitivity is set by a dip switch, which can adapt to leak detection of different water quality;
(9) Provide alarm sound output, which can be turned on or off by setting the dip switch;
(10)Having1Circuit relay output, used for outputting alarm signals or leakage control;
(11)Having2aLEDStatus indication, which can quickly and intuitively understand the working status of the leakage detection system;
(12)The port hasEMCDesign, strong anti-interference ability, and high long-term stability;
(13)DINThe guide rail installation method is convenient for construction and installation;
|
working conditions |
power input |
12VDC, 10V~30VDC |
|
operating current |
≤0.1A |
|
|
ambient temperature |
-30℃~80℃ |
|
|
ambient humidity |
0%~100%RH, non-condensing |
|
|
water leak detection |
Number of detection channels |
2 channels, capable of wire breakage detection function |
|
Cable length |
300m |
|
|
detection sensitivity |
8 sensitivity levels can be set |
|
|
response time |
<2s |
|
|
relay output |
1 way, normally open, contact DC30V 1A |
|
|
Testing water quality |
Ordinary tap water, fire water, and air conditioning leakage |
|
|
RS485 communication interface |
Mailing Address |
1-254, factory default 1 |
|
communication parameters |
9600, N,8,1 |
|
|
communication protocol |
MODBUS RTU protocol |
|
|
EMC index |
Electrostatic protection |
Contact discharge: ± 6KV; Air discharge: ± 8KV |
|
EFT protection |
±2KV |
|
|
external structure |
Length × Width × Height |
108 * 37 * 59 mm (including terminals) |