ADU1100 Battery Monitoring System
  • ADU1100 Battery Monitoring System
ADU1100 Battery Monitoring System
ADU1100电池组电压监控系统是模块式电池监控的低成本解决方案,实时采集电压检测模块的电压、温度、总电流等,经过RS485通信口上送到远程监控系统中。本电池组监控方案主要包含四部分:通信管理模块、电压监测模块、电流传感器、电池温度传感器。

The battery pack monitoring scheme mainly includes four parts: communication management module, voltage monitoring module, current sensor, and battery temperature sensor.

Main functions
(1)Real time collection of voltage and surface temperature of each battery by each module;
(2)Equipped with automatic address allocation function, convenient on-site debugging and maintenance, and strong availability;
(3)Using intelligent analysis technology to provide forecasts for the backup time of battery packs during power outages in the city;
(5) The input port of the battery module is designed with anti reverse and recoverable fuse protection to prevent damage caused by improper construction, ensuring high system safety;
(6)Module structure design allows for flexible configuration of different numbers of battery packs, achievingLow cost solutionPlan;
(7) Provide RS485 communication interface to achieve remote monitoring function, which can be easily integrated into the application systems of third-party companies;
(8)The circuit port has EMC design and strong anti electromagnetic interference capability, especially for UPS battery packs with strong high-frequency interference, which can achieve high measurement accuracy;

Typical System Equipment List

(1) Survey and statistics of battery pack:

computer room name

UPS quantity

Number of battery packs

Number of battery cells per group

Single cell voltage

Diameter of battery bolt

Battery room one

1 unit

1 group

40 sections

12V

10mm

Battery Room 2

1 unit

1 group

192 sections

2V

8mm

……

……

……

……

……

……

(2) List of equipment required to measure a 40 cell UPS battery pack consisting of a standard 12V unit:

name

Module model/specification

quantity

unit

Remarks

Communication management module

BMS50

1

Taiwan

1 module manages 1 set of 48 batteries

Battery collection module

BVS-12(12V)

40

a

12V battery, 1 battery comes with 1 unit

battery connecting wire

JZ40

40

item

Each battery is equipped with one

Collection module communication cable

BL02

40

item

1 battery per cell

Hall Current Sensor

4-20mA signal

1

a

4-20mA output signal

(3) List of equipment required to measure a standard 2V battery pack consisting of 24 UPS cells:

name

Module model/specification

quantity

unit

Remarks

Communication management module

BMS50

1

Taiwan

1 module management1Pack 24 batteries

Battery collection module

BVS-02(2V)

24

a

2V battery, 1 battery comes with 1 unit

battery connecting wire

JZ40

24

item

1 battery paired with 1 unit

Collection module communication cable

BL02

24

item

1 battery paired with 1 unit

Hall Current Sensor

4-20mA signal

1

a

4-20mA output signal

 

The battery pack monitoring scheme mainly includes four parts: communication management module, voltage monitoring module, current sensor, and battery temperature sensor.

Name

Parameters

Remarks

work

condition

input power

12VDC

10~15VDC

power consumption

<3W


ambient temperature

-10℃~50℃


ambient humidity

10%~90%RH, non-condensing


report

Communication port

address range

1-254255 is the broadcast address

Default Address 1

interface method

RS485

Photoelectric isolation

communication parameters

9600、 N、8、1


battery

collect

interface

Number of batteries

48section

RJ11interface

interface method

current loop

Photoelectric isolation

communication parameters

9600、 N、8、1


current

sensor

Number of collection channels

1road

Test 1 set of batteries

input signal

4~20mA


Collection accuracy

1% FS

Related to sensor accuracy

alternate route

Number of collection channels

2road


input signal

0-2.5V


Collection accuracy

1% FS

Related to sensor accuracy