(1) Advanced internal resistance detection technology - small signal pulse AC method, real-time online monitoring and analysis of the trend of internal resistance changes in batteries, predicting outdated batteries in battery packs;
(2)High security. Equipped with multiple protections such as power isolation, optocoupler isolation, and fuse protection, it does not affect the operation of the battery pack;
(3)Real time collection of voltage, internal resistance, temperature, and total current of each battery cell;
(4)The battery monitoring module address has an automatic allocation function, making debugging "foolproof" and simple and practical;
(5)Reserve one analog acquisition channel, connected to 4-20mA sensor signals, for detecting environmental temperature, mains voltage and other parameters;
(6)Dual watchdog design with self recovery function and strong stability;
(7)Provide early prediction of the operating status of the battery pack, and provide reliable basis for battery maintenance or replacement;
(8)The circuit port has EMC design and strong anti electromagnetic interference capability, especially for high-frequency UPS battery packs, which can achieve high measurement accuracy;
(9)Provide RS485 communication port to achieve remote monitoring function and facilitate access to third-party company application systems.
BMS200Communication management module |
Name | Parameters | Remarks |
working conditions | input power | 10~15VDC | Power supply for communication management module |
power consumption | <3W | Maximum module power consumption |
ambient temperature | -10℃~50℃ |
|
ambient humidity | 10%~90%RH, non-condensing |
|
Report communication port | address range | 1-254255 is the broadcast address |
|
interface method | RS485 | Photoelectric isolation |
communication parameters | 9600 N、8、1 |
|
Battery communication port | Number of batteries | 250 | BMS-02 module |
bus interface | RJ11-4P4C interface |
|
interface method | current loop | Photoelectric isolation |
communication parameters | 9600 N、8、1 |
|
current sensor | input signal | 4~20mA |
|
Collection accuracy | 1% FS | Related to sensor accuracy |
Backup simulation channel | input signal | 4~20mA, External sensors |
|
EMC Metrics | ESD protection | Contact discharge: ± 6KV Air discharge: ± 8KV |
|
EFT protection | ±2KV |
|
external structure | L*W*H | Product: 117 * 72 * 35 (including terminals) | Packaging: 150 * 85 * 50mm |